TALK TO AN EXPERT: 1-844-945-3625

0

Your Cart is Empty

How to Size a Battery Bank for Home Backup Power

by Cliff Co 8 min read

 

Battery bank sizing is the step where most home backup systems go wrong in both directions. Too small and the system runs out of power before the outage ends. Too large and you have spent several thousand dollars on capacity you will never use. Getting it right requires three things: an honest accounting of what you actually need to run, a clear decision on how many days of backup you want, and an understanding of how depth of discharge affects what you can actually use from the battery you buy.

This guide walks through the sizing process step by step, with a real appliance wattage table, worked examples for three different household types, and the most common mistakes that lead to undersized or oversized systems. Browse our generator batteries collection once you have your target capacity.

Jackery Battery Pack 2000 Plus with explorer 2000 plus outdoors

Key Takeaways
  • The sizing formula is: Battery bank (Wh) = Daily load (Wh) x Days of autonomy / Depth of discharge (0.8 for LiFePO4, 0.5 for AGM).
  • Only count the loads you actually need during an outage, not every appliance in your home. The difference between "essentials" and "everything" is often 5 to 10 times the energy consumption.
  • Depth of discharge is why a 200Ah LiFePO4 bank effectively gives you twice the usable energy of a 200Ah AGM bank. The Ah rating on the label is not the same as usable capacity.
  • Add a 20 to 30 percent buffer over your calculated minimum. Sizing exactly to the minimum leaves no margin for cold weather derating, inefficiencies, or an unexpected load being added.

Why Sizing Matters: Undersized vs. Oversized

An undersized battery bank runs out before the outage ends. In a multi-day storm scenario, that means reverting to the exact situation you were trying to avoid. An oversized bank means you have paid for capacity that sits unused through every outage you actually experience, which for most households means most of the time. Both outcomes are avoidable if the sizing is done correctly upfront.

The goal is a system that handles your real-world worst-case scenario with a reasonable margin, not a system sized for the absolute worst winter storm imaginable, and not one sized for a sunny afternoon test run.

Step 1: List Your Critical Loads

Write down every appliance you genuinely need to run during a power outage. Be honest and be selective. Most households do not need to run their electric oven, clothes dryer, or electric vehicle charger during an outage. What most households do need:

Appliance Typical Running Watts Notes
Full-size refrigerator 150 to 200W when compressor runs; 50 to 80W continuous average Compressor cycles on/off at 30 to 50% duty cycle. Actual daily use: 400 to 800 Wh for modern Energy Star models, 1,000 to 1,500 Wh for older units. Do not multiply running watts by 24h: use your model's annual kWh label divided by 365.
LED lighting (8 bulbs) 80 to 100W 10W per LED bulb is typical for 60W equivalent
WiFi router 10 to 20W Runs 24h during an outage if internet stays up
Phone and tablet charging (2 to 4 devices) 25 to 60W Actual draw is low; negligible over a day
LED TV (55 inch) 60 to 100W Used for news/information during outage
CPAP machine (no heater) 30 to 40W With heated humidifier: 45 to 70W
Well pump (1/2 HP) 750 to 1,000W running Starting surge can be 2,000 to 3,000W; check your inverter's surge rating
Window AC (5,000 BTU) 450 to 600W Significant load; adds substantially to daily Wh if run for hours
Box fan 40 to 100W Much more efficient than AC for comfort cooling
Sump pump (1/3 HP) 400 to 800W running Intermittent; only runs when activated

Starting wattage vs. running wattage matters for motors (pumps, compressors, AC units). Motors draw 2 to 3 times their running wattage for a brief moment at startup. Your inverter needs to handle the starting surge; your battery sizing is based on running wattage and duration.

Step 2: Calculate Your Daily Wh Consumption

For each appliance on your list, multiply running watts by the number of hours per day you expect to run it. Add the results together.

Formula: Appliance Wh = Running Watts x Hours per Day

Example for a typical essential-loads setup:

Appliance Running Watts Hours/Day Daily Wh
Refrigerator See notes 24h 1,500 Wh (est. for older unit)
LED lighting 80W 6h 480 Wh
WiFi router 15W 24h 360 Wh
Phone charging 30W 3h 90 Wh
TV 80W 4h 320 Wh
Total daily load 2,750 Wh

Note: The refrigerator figure above (1,500 Wh) is an estimate for an older full-size unit. Modern Energy Star models use 400 to 800 Wh/day. Check your model's energy label (annual kWh / 365) for an accurate figure rather than multiplying the compressor's running watts by 24 hours.

Step 3: Choose Your Autonomy Window

Autonomy is how many days you want the battery to run your essential loads with no solar recharge and no generator input. This is the worst-case scenario your system needs to handle.

  • 1 day (24 hours): Covers short outages and overnight gaps between solar recharge periods. Appropriate for areas with reliable utility restoration and a solar system that recharges the bank daily.
  • 2 to 3 days: The practical target for most home backup systems in storm-prone areas. Covers most weather-related outages without requiring a generator as a backup.
  • 5 to 7 days: Extended off-grid autonomy, appropriate for remote properties or areas with historically long outage durations. Requires a significantly larger battery bank and typically a solar system or generator for recharge.

Step 4: Account for Depth of Discharge

Depth of discharge (DoD) is the percentage of a battery's rated capacity that can safely be used before recharging. This is where most sizing calculations go wrong. The Ah or Wh number printed on a battery label is the total capacity, not the usable capacity.

LiFePO4 DoD: 80%. A 100Ah LiFePO4 battery gives you 80Ah of usable energy per cycle. Divide your energy requirement by 0.8.

AGM DoD: 50%. A 100Ah AGM battery gives you 50Ah of usable energy per cycle. Divide your energy requirement by 0.5.

The sizing formula:

Battery Bank (Wh) = Daily Load (Wh) x Days of Autonomy / DoD

Using the example from Step 2 (2,750 Wh/day), for a 2-day LiFePO4 system:

2,750 Wh x 2 days / 0.8 = 6,875 Wh required bank capacity (6.9 kWh)

For the same load with a 2-day AGM system:

2,750 Wh x 2 days / 0.5 = 11,000 Wh required bank capacity (11 kWh)

The DoD difference means you need 60 percent more AGM capacity to deliver the same usable energy as LiFePO4, which largely explains why LiFePO4 is more cost-effective at scale despite its higher unit price.

Step 5: Adjust for Solar Input

If your battery bank is paired with solar panels, you can subtract the expected daily solar generation from your daily load before calculating autonomy. A 400W solar array in a location averaging 4 peak sun hours per day produces approximately 1,600 Wh per day. Applied to the 2,750 Wh/day example load, that reduces the net daily draw to 1,150 Wh, which reduces the required bank size proportionally for multi-day scenarios.

In winter, reduce your solar production estimate significantly: shorter days, lower sun angles, and potential snow coverage can cut effective production by 50 to 70 percent compared to summer figures in most northern US locations.

Sample Sizing by Household Type

Household Type Daily Load Est. Autonomy Target LiFePO4 Bank Needed Example Product
Apartment / Small home, essentials only (fridge, lights, router, devices) 1,500 to 2,000 Wh/day 1 to 2 days 2 to 5 kWh EcoFlow DELTA Pro (3.6kWh) or Rich Solar ALPHA 2x 200Ah
3-bed home, essentials plus TV and CPAP 3,000 to 5,000 Wh/day 2 to 3 days 8 to 19 kWh EcoFlow DELTA Pro + Smart Extra Battery (7.2kWh), or two units
Full home backup including well pump and summer AC 6,000 to 10,000 Wh/day 1 to 2 days 8 to 25 kWh EcoFlow DELTA Pro Ultra system with expansion batteries

Common Sizing Mistakes

Sizing for the average day instead of the worst day. Battery backup is not for the typical Thursday; it is for the ice storm in February when the power stays out for three days. Size for the worst realistic scenario, not the median outage duration in your area.

Forgetting starting surge for motors. A well pump, sump pump, or refrigerator compressor draws 2 to 3 times its running wattage for a brief moment at startup. Your battery bank handles sustained load fine, but your inverter must handle the startup surge. Confirm the inverter's surge rating covers the largest motor on your list.

Not accounting for DoD. Treating a 10 kWh battery bank as 10 kWh of usable energy is a sizing error. A 10 kWh LiFePO4 bank gives you 8 kWh of usable energy. A 10 kWh AGM bank gives you 5 kWh. The difference is large enough to fundamentally change which products you need to buy.

Ignoring cold weather derating. If your battery bank is in an unheated space in a cold climate, plan for 80 to 90 percent of rated capacity at 32°F and less in colder conditions. A system that barely meets your needs in summer may fall short in the outage that happens during a February ice storm.

Adding 20 to 30 percent buffer. Sizing exactly to the calculated minimum leaves no margin. Build in a buffer that covers the uncertainty in your load estimates, cold weather derating, and the possibility of one more appliance being added later.

Frequently Asked Questions

How do I calculate how much battery I need for home backup?

Add up the wattage of every appliance you need to run during an outage, multiply each by the hours per day you will run it, and total the results to get your daily watt-hours. Multiply by your desired days of autonomy, then divide by your battery's usable depth of discharge (0.8 for LiFePO4, 0.5 for AGM). The result is the minimum battery bank capacity in watt-hours you need.

How many kWh do I need to power a house for a day?

For essential loads only (refrigerator, lighting, device charging, and a router), a typical household uses roughly 2 to 3 kWh per day. Adding a well pump, window AC, or other larger loads can push that to 5 to 8 kWh or more per day. The US Energy Information Administration reports the average US home uses about 30 kWh per day total, but running everything on backup is neither necessary nor practical for most outage scenarios.

What is depth of discharge and why does it affect battery sizing?

Depth of discharge (DoD) is the percentage of a battery's rated capacity that can be used before recharging without damaging the cells. AGM batteries are limited to 50 percent DoD, meaning a 200Ah AGM bank only gives you 100Ah of usable energy. LiFePO4 can be used to 80 to 100 percent, so a 200Ah LiFePO4 bank gives you 160 to 200Ah. When sizing a battery bank, you must divide your energy requirement by the DoD to find the total rated capacity you need to buy.

How many batteries do I need for a 3-day backup?

For a household running essential loads at 2,500 Wh per day for 3 days of autonomy with a LiFePO4 battery bank: 2,500 x 3 = 7,500 Wh needed, divided by 0.8 DoD = 9,375 Wh required bank capacity, which is approximately 9.4 kWh. Two EcoFlow DELTA Pro units each with one Smart Extra Battery would provide about 14.4 kWh, comfortably exceeding that requirement with margin.

Should I oversize my battery bank?

Yes, in most cases. Sizing exactly to your calculated minimum leaves no margin for cold weather derating, unexpected loads, or system inefficiencies. A 20 to 30 percent buffer over the calculated minimum is a reasonable practical recommendation, particularly for LiFePO4 systems in cold climates where winter capacity may be 80 percent of rated.

Cliff Co
Cliff Co

Cliff, a passionate storyteller and hardcore seller, here to share insights and knowledge on all things prep. He firmly believes in only selling things he'd use himself, making sure only the best get to his readers' hands.

Leave a comment

Comments will be approved before showing up.